Commercial/Demanding
Residential for Hot Water or Steam

The perfect alternative to bulky, commercial enclosures for demanding heat requirements. Especially suited to problem areas of high heat loss. 18 Guage standard front covers.

*Stocked in 2-3-4-5-6-7-8-10 foot lengths, both complete (with elements) and enclosure only (less element).



Table 1 - Heating Capacities, BTU per hr per lin. ft. 65 degrees entering air temperature I-B-R approved 

Model

Nom. Tube Size

Fin
Dimensions
H X W

Thick-
ness

Fin
Spacing
Fins/Ft.

Dimension
'A'

Water
Rate
GPM

Hot Water Ratings
Average Water Temperature degrees F 

Supr-
Heat
1000-
1A

3/4"
CPR.

2 1/2" X 3 1/4"
Alum Natural Finish

.015

55

3 5/8"

4

1

150

160

170

180

190

200

210

220

230

240

630

740

850

950

1050

1150

1260

1360

1470

1570

600

700

800

900

990

1090

1190

1290

1390

1490

Supr-
Heat
1000-
S125

1 1/4"
IPS
Steel

3 1/4" X 3 1/4"
Painted

Steam BTU.
1130 sq ft/hr 4.7

.029

48

3 7/8"

4

1

510

600

700

790

890

970

1070

1160

1260

1350

480

570

660

750

840

920

1010

1100

1190

1280

Supr-
Heat
1000-
3A

1 1/4"
CPR.

3" X 3 1/4"
Alum. Natural Finish

Steam BTU.
1300 sq ft/hr 5.4

.020

54

3 7/8"

4

1

580

690

790

900

1000

1110

1220

1310

1420

1520

550

650

750

850

950

1050

1150

1240

1340

1440
All the above I-B-R Ratings are based on active length, which is 3" less than total length, and includes a 15% addition for heating effect.
Ratings: Heating capacities are listed in Table 1 for two flow rates: 1 GPM and 4 GPM. The use of I-B-R Ratings at 4 GPM is limited to installations where the water flow rate through the baseboard unit is equal to or greater than 4 GPM. Where the water flow rate through the baseboard is not known, the I-B-R Ratings at the standard flow of 1 GPM must be used.

Table 2 - Factors for ratings at flow other than standard and pressure drop values

Rate of Flow GPM

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

6.0

Factor

1.000

1.016

1.028

1.038

1.045

1.051

1.057

1.062

1.067

1.074

Pressure Drop 3/4" Copper Tube
Mill inches per ft.

47

96

157

230

320

420

525

650

775

1060

Pressure Drop 1 1/4" IPS Steel Pipe
Mill in. per ft.

3

7

12

17

24

32

41

51

62

88

Pressure Drop 1 1/4" Copper Tube
Mill inches per ft.

6

12

20

28

39

50

63

77

93

124

Note: If the calculated water flow rate through a baseboard unit in a completely designed hot water heating system is greater than the standard flow rate (1 GPM), the rating of that unit may be increased by multiplying the standard I-B-R Rating at 1 GPM by the factor shown for the calculated flow rate.